Transformer Oil DGA Monitoring Technology Study

Online Monitoring

An 18-month, multi-technology evaluation of dissolved gas analysis (DGA) monitors — measuring detection accuracy, gas-change sensitivity, and real-world suitability for transformer maintenance programs.

  • Authors: Jason C. Dennison & Jon M. Trout, PE — SDMyers
  • Study Duration: 18 Months
  • Experiments Conducted: 30+
  • Published: 2015
  • Technologies Evaluated: 5 Monitor Types

Download the Study

This field is for validation purposes and should be left unchanged.

What Is DGA Monitoring — and Why Does It Matter?

Dissolved gas analysis (DGA) is the cornerstone diagnostic tool for detecting incipient faults in oil-filled power transformers. As transformer monitoring technology advances, DGA monitors — devices that continuously sample and analyze fault gases dissolved in insulating oil — are becoming a standard component of modern reliability programs.

With the DGA monitor market projected to grow from $113M in 2012 to over $755M by 2020, transformer owners and maintenance teams face a critical question: do these monitors actually agree with conventional laboratory results, and can they reliably detect dangerous gas changes in the field?

SDMyers conducted this rigorous 18-month study to answer exactly that — evaluating the real-world performance of five major DGA monitoring technologies under controlled, repeatable laboratory conditions.

Technologies Evaluated in This Study

Seven monitor configurations representing five core technology platforms were tested head-to-head against conventional laboratory gas chromatography (GC) — the current IEEE-referenced standard for DGA in oil-immersed transformers.

AbbreviationTechnology
GCGas Chromatography
PASPhoto-Acoustic Spectroscopy
SS-PdSolid-State Palladium
TCDThermal Conductivity Detection
SMSelective Membrane
Lab GC (Reference)Conventional Laboratory GC

Key Findings: What Maintenance Technicians Need to Know

Detection Performance

  • All five technologies successfully detected fault gas changes from a steady-state baseline — confirming that continuous DGA monitoring is a viable tool for early fault detection regardless of the platform used.
  • PPM values varied between monitors and conventional lab GC, but this variability was consistent with known inter-laboratory variation. It is not a disqualifying flaw, but it does demand expert interpretation.
  • No single technology outperformed all others in consistently matching conventional lab GC results across all experiments. Technology selection should be driven by application, not brand assumptions.
  • Detecting changes from a baseline is more critical than absolute PPM accuracy. All monitors excelled at this core function, making rate-of-change monitoring a reliable early-warning strategy.

Hydrogen Monitoring — Special Considerations

  • Hydrogen is the most universal fault indicator, generated in the majority of active fault conditions, making H2 monitors a popular lower-cost entry point into DGA monitoring.
  • Alert and alarm thresholds must be set carefully. Setting sensitivity too low generates nuisance alarms from natural H2 variation; too high risks missing low-level arcing faults. Expert calibration is essential.
  • Selective membrane (SM) monitors exhibited a “tailing lag” when returning to baseline H2 levels after a gas event — due to the higher solubility of CO and acetylene in oil. This does not impair fault detection but affects how return-to-normal readings are interpreted.
  • Hydrogen monitors function best as a “check engine light,” not a definitive diagnostic. Any triggered alarm should prompt expert DGA review, not automated action alone.

Data Volume & Management

  • Continuous monitors generate orders of magnitude more data than routine interval testing. A single-gas monitor sampling every 20–30 minutes produces over 52,000 data points per year versus 12 data points from annual lab testing.
  • Multi-gas monitors capture additional parameters including oil temperature, load current, pressure, and moisture — enabling richer diagnostic correlation.
  • Data management infrastructure must be planned before deployment. Monitors not connected to a network create retrieval bottlenecks; unmanaged data rapidly becomes unusable without dedicated expertise.
  • Software platforms offered by monitor manufacturers vary widely in diagnostic capability. Owners should evaluate data management tools as part of the purchase decision.

Key Findings: What Transformer Owners Need to Know

  • DGA monitoring is a supplement to routine maintenance, not a replacement. Variability in monitor-to-lab PPM alignment reinforces that conventional laboratory testing, periodic inspection, and online monitoring should be used together.
  • DGA expertise is non-negotiable. The volume and complexity of monitor data requires qualified analysts to contextualize readings, correlate trends, and recommend appropriate responses — especially when alarms trigger.
  • Monitors increase the value of every maintenance dollar by enabling predictive, condition-based interventions rather than reactive repair — but only when the data is properly interpreted and acted upon.
  • Early procurement planning matters. Specifying monitors at the time of new transformer purchase is now common practice; retrofitting to in-service critical transformers is an increasingly important reliability investment.
  • Market growth signals a maturing technology. With adoption expanding from utilities and generation into industrial and grid-wide applications, DGA monitoring is rapidly becoming standard practice across transformer ownership.

EXPERT INSIGHT

Responding to potential incipient issues based on expert judgment of DGA and all available information is the foundation for a cost-effective, intelligent reliability approach to transformer maintenance.

— Dennison & Trout, SDMyers DGA Monitoring Technology Study, 2015

Study Methodology at a Glance

Element Detail
Test Tank80-gallon steel tank, 60 gallons of oil
Oil TemperatureMaintained at 60°C (140°F) with thermocouples
Oil ConditionContinuously circulated and mixed
Number of Experiments30+ over 18 months
Reference ComparisonConventional lab GC via co-located sample port
Monitor ConfigurationInstalled and configured by manufacturers
Between-Run ResetVacuum degasser to return oil to baseline

Bottom Line for Transformer Programs

This study confirms that all major DGA monitor technologies are competent at their most critical function: detecting when something changes in a transformer’s dissolved gas profile. The technology choice is less important than the operational framework around it — how alarms are set, how data is managed, and whether qualified DGA expertise is applied to interpretation.

For organizations building or expanding transformer reliability programs, this guide provides the technical foundation needed to evaluate DGA monitor platforms, set realistic performance expectations, and design a monitoring strategy that integrates seamlessly with conventional maintenance practices.

STUDY AT A GLANCE

Metric Value
Study Duration18 Months
Experiments Conducted30+
Technologies Evaluated5
Gases Monitored9
Annual Data Points (single-gas mon.)52,000+

TOPICS COVERED IN THE FULL GUIDE

  • Monitor-to-lab PPM comparison
  • Gas detection & change sensitivity
  • Hydrogen monitoring best practices
  • Alarm/alert threshold setting
  • Data generation & management
  • Technology selection guidance

On this page

Talk to an Expert

Get expert guidance on diagnostics, maintenance, and reliability planning for your transformer fleet.

SHARE:

Different look

Same SDMyers

Welcome to our new site! Same team. Same expertise. A sharper site built to get you to the answers that keep your transformers running.